We develop and produce high performance electricity meters, power analyzers, current sensors, communication modules and management systems. RS485 Modbus Class 0.5S Panel Mounted Multi-function Power Analyzer Manufacturers and Factory
400-996-9296
Eastron Smart X96-5S is a new generation panel mounted multi-function power analyzer, serving as a digital monitoring terminal and an intelligent device integrating measurement, monitoring, and communication. It utilizes modern computer and digital signal processing technology, enabling it to replace various transmitters, meters, relays, and other components. The multi-function power analyzer features an RS-485 interface and supports the standard MODBUS-RTU communication protocol, allowing seamless integration into any power monitoring system.
Eastron Smart X96-5S is designed for power monitoring applications in power systems, industrial and mining enterprises, public facilities, and smart buildings. It measures all common electrical parameters, such as three-phase current, voltage, active and reactive power, and energy consumption, making it highly suitable for real-time power monitoring systems.
With an excellent performance-to-price ratio, the Smart X96-5S can directly replace conventional power transmitters and measurement instruments. As an advanced intelligent and digital front-end acquisition component, it is widely applicable in various control systems, SCADA systems, and energy management systems.
|
Electrical characteristics |
||
|
Type of measurement |
RMS including harmonics on three phase AC system (3P, 3P+N) |
|
|
Measurement accuracy |
Active power |
±1% |
|
Reactive power |
±1% |
|
|
Apparent power |
±1% |
|
|
Active Energy |
Class 0.5S IEC 62053-22 Class C EN50470-3:2022 |
|
|
Reactive Energy |
Class 2 IEC 62053-23 |
|
|
Frequency |
±0.2% |
|
|
Current |
±0.2% |
|
|
Voltage |
±0.2% |
|
|
Power Factor |
±0.01 |
|
|
Input & Output |
|||
|
Input |
Current |
Rated Current |
5A |
|
Max Current |
6A |
||
|
Min Current |
0.05A |
||
|
Starting Current |
50mA |
||
|
Voltage |
Aux. power supply |
100~480V AC / 141~678V DC |
|
|
Measured voltage |
50V ~ 600V AC (L-L) 50V ~345V AC (L-N) |
||
|
Communication |
Interface 1 |
RS485 |
|
|
Protocol |
Modbus-RTU |
||
|
Baud rate |
2400bps ~ 115200 bps, default: 9600 bps |
||
|
Address |
1 to 247 |
||
|
Pariy |
None (default), Even, Odd |
||
|
Stop Bit |
1 or 2 |
||
|
Interface 2 |
Ethernet |
||
|
Protocol |
Modbus-TCP |
||
|
IP |
192.168.1.200 (default) |
||
|
Port |
502 |
||
|
Mask |
255.255.255.0 |
||
|
Gateway |
192.168.1.1 |
||
|
DHCP |
OFF (default) |
||
|
Mechanical Characteristics |
|
|
Weight |
322g |
|
IP Degree of Protection (IEC 60529) |
IP51 front display |
|
Dimensions (WxHxD) |
96x96X73.5 mm |
|
Panel cut-out |
Vertical |
|
Material of meter case |
Self-extinguishing UL 94 V-0 |
|
Environmental Characteristics |
|
|
Operating Temperature |
-25 to 75°C |
|
Storage Temperature |
-40 to 85°C |
|
Humidity Rating |
<95% RH (non-condensing) |
|
Pollution Degree |
2 |
|
Altitude |
2000m |