Need Help? - Call: 0086-573-8369881/8369882 or email: sales@eastrongroup.com

中文版English

  • SDM120CT-Modbus CT operated Multifunction Single Phase Energy Meter With RS485 Communication

    • Measures kWh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.
    • Bi-directional measurement IMP & EXP
    • Two pulse outputs
    • RS485 Port modbus RTU
    • 17.5 mm width 1 modual
    • CT operated
    • Class 1.0 accuracy
    • Din rail Mounted
    • Description
    • Diagram
    • Manual Download

    Application


    The energy-meters “with a white back-lighted LCD screen for prefect reading” are used to measure single-phase like residential, utility and Industrial application. The unit measures and displays various important electrical parameters, and provide a RS485 communication port for remote reading and monitoring. Bi-directional energy measurement makes the unit a good choice for solar PV energy metering. The compact design and din rail installation provides a easy and economical solution for your metering demand.

    General Specifications

    Voltage AC (Un) 230V
    Voltage Range  176~276V AC
    Base Current (Ib)   0.1VAC
    Power consumption  <2W/10VA
    Frequency   50/60Hz(±10%)
    AC voltage withstand  4KV for 1 minute
    Impulse voltage withstand  6KV-1.2uS wavform
    Overcurrent withstand  30Imax for 0.01s
    Pulse output rate  1000imp/kWh (default)
    0.001(default) /0.01/0.1/1/10/100/1000 kWh/kVarh (configurable)
    Display  LCD with white backlit
    Max. Reading  99999.9kWh


    Accuracy

    Voltage 0.5% of range maximum
    Current 0.5% of nominal
    Frequency   0.2% of mid-frequency
    Power factor 1% of Unity
    Active power   1% of range maximum
    Reactive power   1% of range maximum
    Apparent power  1% of range maximum
    Active energy  Class 1 IEC62053-21
    Class B EN50470-3
    Reactive energy  1% of range maximum



    Environment

    Operating temperature   -25℃ to + 55℃
    Storage and transportation temperature  -40℃ to +70℃
    Reference temperature 23℃±2℃
    Relative humidity   0 to 95%, non-condensing
    Altitude  up to 2500m
    Warm up time  10s
    Mechanical Environment M1
    Electromagnetic environment E2
    Degree of pollution  2


    Output

    Pulse Output

    The meter provides two pulse outputs. Both pulse outputs are passive type.

    Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total /import/ export kWh or kVarh.

    The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1/10/100/1000 kWh/kVarh.

    Pulse width: 200/100/60ms

    Pulse output 2 is non-configurable. It is fixed up with total kWh. The constant is 1000imp/kWh.



    RS485 output for Modbus RTU

    The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus RTU, the following RS485 communication parameters can be configured by the Modbus command. 

    Baud rate: 1200, 2400, 4800, 9600

    Parity: NONE/EVEN/ODD

    Stop bits: 1 or 2

    Modbus Address: 1 to 247


    Mechanics

    Din rail dimensions   17.5x119x62 (WxHxD) DIN 43880
    Mounting  DIN rail 35mm
    Sealing   IP51 (indoor)
    Material Self-extinguishing UL94V-0